Medium voltage distribution:
Two medium voltage circuit breakers with commutation and protective devices placed in SF6 filled container. Up to 3 cable connections and with one transformer connection. Transformer protection with fuses.
Transformer chamber:
Hermetic oil transformer Smax – 630 kVA, 10(20)/0,42 kV, maximum transformer dimension – 2800x1450x0 mm.
Low voltage distribution::
Inlet: | Fuse switch In – 1250A with NH-4a gabarit fuse inserts |
Sectioning | Fuse switch In – 1250A with NH-4a gabarit fuse inserts. |
Alternative: Load switch In – 1250 A |
|
Feeders |
Fuse switches In – 400A with NH-2 gabarit fuse inserts Alternative: Fuse switch In – 160A with NH-00 gabarit fuse inserts Fuse switch In – 630A with NH-3 gabarit fuse inserts |
Additional options
- It is possible to prepare the low voltage distribution with a partition wall and separated doors;
- Remote reading of electricity registers and meters;
- Alarm (smoke detector, door opening alarm);
- Other colour tone and texture of housing..